Part Number Hot Search : 
X9420WPM HCT57 1M35V10 74HC7 038FB 05000 TPD1036F VCO55CL
Product Description
Full Text Search
 

To Download M02-04-00 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 SS-PD and SS-PDR
Intelligent Low-Flow Photoelectric Duct Smoke Detectors
SS-PD
Features
* Air velocity rating from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec.). * Patented telescopic sampling tube.
Description
* Easily accessible code wheels for addressing detector. * Outside mounting tabs. * Mounts to round or rectangular ducts from 1' to 12' (0.3 to 3.7 meters) wide. * Transparent cover for convenient visual inspection.
The Gamewell SS-PD and SS-PDR Intelligent Low-Flow Photoelectric Smoke Duct Detectors provide lowflow technology that enables duct smoke detection throughout a broad range of airflow environments in HVAC applications. The low-flow technology SS-PDR can detect smoke at air speed velocities of 100 feet per minute (0.5 m/sec.) or greater, while continuing the same reliable performance to 4,000 feet per minute (20.32 m/sec.). The intelligent low-flow duct detectors sample air currents passing through a duct and gives dependable performance for shutdown of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke an fire gases through the protected area. The SS-PD and SS-PDR provide a remote alarm output for use with auxiliary devices such as the RA400 remote LED annunciator, as well as remote test capability with the RTS451 or RTS451KEY Remote Test Stations. The SS-PD is a photoelectric duct detector with SmartScanTM protocol. The SSPDR additionally incorporates a relay.
Listings
Listings and approvals below apply to the SS-PD and SSPDR Intelligent Low-Flow Photoelectric Duct Smoke Detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. * UL Listed: file S1115. * CSFM approved: file 3240-1288:167. * MEA approved: file 384-02-E Vol. III.
Applications
Duct smoke detectors have specific limitations, they are: * NOT a substitute for open area smoke detectors. * NOT a substitute for early warning detection. * NOT a replacement for a building's regular fire detection system. Please call Gamewell for a copy of System Sensor's application guide, Proper Use of Smoke Detectors in Duct Applications, (A05-1004-00).
Installation
Wiring: For signal wiring (the wiring between detectors or from detectors to auxiliary devices), it is recommended that single conductor wire be no smaller than 18 AWG (0.75 mm). The duct smoke detector terminals accommodate wire sizes up to 12 AWG (3.25 mm). Flexible conduit is recommended for the last foot (30.48 cm) of conduit; solid conduit connections may be used if desired. Smoke detectors and alarm system control panels have specifications for Signaling Line Circuit (SLC) wiring. Consult the control panel specifications for wiring requirements before wiring the detector loop. The SS-PD and SS-PDR detectors are designed for ease of wiring; their housing provides a terminal strip with clamping plates. LED Features: If programmed with the system control panel, two LEDs on each duct smoke detector light to provide local visible indication.
SS-PD and SS-PDR
CS-2463
10/21/04
Page 1 of 4
Programming specifications requirements for intelligent system control panels:
The number of devices that can have their LEDs programmed to illuminate is limited by the features of the panel and the individual devices. The actual number of devices is determined by the control panel and its ability to supply LED current. Refer to the control panel installation manual for details.
SS-PD: Current Requirem ents (us ing no access ories) Pow e r 24VAC, 120VAC, 220/240 VAC, Supply 30-30VDC 50/60 Hz 50/60 Hz 50/60 Hz Voltage Max. 65 mA 44 mA 25 mA RMS Standby 26 Ma RMS RMS Current Max Alarm 182 mA 52 mA 87 mA 30 mA RMS Current RMS RMS Alarm 3 to 17 3 to 17 3 to 17 Response 3 to 17 Sec. Sec. Sec. Sec. Tim e Pow e r Up 2 Sec. 2 Sec. 2 Sec. 2 Sec. Tim e
Specifications
SS-PD
Operating voltage range 15 to 32 VDC. Standby current 300 A @ 24 VDC (one communication every 5 seconds with LED blink enabled). Operating temperature range 32 to 131F (0 to 55C). Relative Humidity range 10% to 93% (non-condensing). Duct air velocity 100 to 4,000 feet/min (0.5 to 20.32 m/s). Dimensions 14.750" (37 cm) length x 5.500" (14 cm) width x 2.750" (7 cm) deep. Options 1. RTS-451, RTS-451KEY, RA400Z. 2. PA400 (Review installation instructions on power requirements).
SS-PDR: Relay Contact Ratings 10 Amp @ 30 VDC Alarm Auxiliary Contacts * (DPDT) Supervisory Contact (SPST) 10 Amp @ 277 VAC (0.75 Pow er Factor) 240 VAC @ 249 VAC (0.4 Pow er Factor) 1/8 HP @ 120 VAC 1/4 HP @ 240 VAC 2.0 Amp @ 30 VDC (resistive)
Minimum sw itching current of 100 mA @ 5 VDC.
Product Line Information
Model SS-PD SS-PDR A5053GM A5067 A5060 ST-1.5 ST-3 ST-5 ST-10 RA400Z RTS451 Description Duct detector housing with SmartScanTM photoelectric smoke detector. Duct detector housing with SmartScanTM photoelectric smoke detector, DPDT relay. Replacement photoelectric sensor board. Replacement power board (without relay). Replacement power board (with relay). Metal sampling tube, duct widths 1' to 2' (see table at left for metric lengths). Metal sampling tube, duct widths 2' to 4'. Metal sampling tube, duct widths 4' to 8'. Metal sampling tube, duct widths 8' to 12'. Remote annunciator alarm LED. Remote test station. Mounts in single-gang box. Includes red alarm LED and magnet test switch. Key-activated remote test station. Replacement filters. Replacement test magnet. Replacement photo insect screen.
SS-PDR
Operating voltage range 20 to 30 VDC, 24 VAC/VDC, 120/ 240 VAC auxiliary power (requires a separate auxiliary source). Standby current 300 A @ 24 VDC (one communication every 5 seconds with LED blink enabled). Operating temperature range 32 to 131F (0 to 55C). Relative Humidity range 10% to 93% (non-condensing). Duct air velocity 100 to 4,000 feet/min (0.5 to 20.32 m/s). Dimensions 14.750" (37 cm) length x 5.500" (14 cm) width x 2.750" (7 cm) deep. Options 1. RTS-451, RTS-451KEY, RA400Z. 2. PA400 (Review installation instructions on power requirements).
The RA400Z
The RTS451
RTS451KEY F36-09-11 M02-04-00 S08-39-01
The RTS451KEY
Page 2 of 4 SS-PD and SS-PDR CS-2463 10/21/04
Sample Wiring Diagrams
SS-PD Duct Smoke Detector using a UL Listed control panel
On to other Detectors on the Loop
6821wir1.wmf
SS-PD Detector Terminals
SS-PD Duct Smoke Detector with optional RA400Z
6821wir2.wmf
SS-PD Duct Smoke Detector with RTS451/ RTS451KEY
NOTE: For RTS451, Terminal 3 is not used. RTS451 does not have a Terminal 6. For RTS451KEY, Terminals 3 and 6 are not used.
SS-PD Detector Terminals
SS-PD
Please refer to manual I56-1978-002R for installation instructions.
SS-PDR
6821wir3.wmf
Please refer to manual I56-1979-003R for installation instructions.
Outside Duct Width
Up to 2 feet (0.6096 m) 2 to 4 feet (0.6096 to 1.2192 m) 4 to 8 feet (1.2192 to 2.4384 m) 8 to 12 feet (2.4384 to 3.6576 m)
Inlet Tube*
ST-1.5 ST-3 ST-5 ST-10
*NOTE: Inlet tube is required and must be purchased separately. Order one inlet tube for each duct smoke detector ordered.
SS-PD and SS-PDR
CS-2463
10/21/04
Page 3 of 4
The Gamewell Company 12 Clintonville Road Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell.com A Honeywell Company (c) 2004 Gamewell
Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell.
Page 4 of 4 SS-PD and SS-PDR CS-2463 10/21/04


▲Up To Search▲   

 
Price & Availability of M02-04-00

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X